Combined protection device 2in1 for CCTV camera systems

Item no. 5081070 | EAN 4012196676965

  • 5-year warranty
  • Transition from LPZ 0 to LPZ 2
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • Category 5 TwisterPair
  • TV applications
  • Installation electrotechnical expertise

Combination protection device for IP-based TV/camera systems

• Protection of power and data interface in a single device
• In aluminium housing
• Simple mounting with adapter plug
• Two-stage protection circuit
• Three-pole power connection for the power interface
• RJ45 connection for the data interface
• With LED operation display (OS)
• Incl. DIN rail fastening set

Application: Protection of CCTV, video signals, (IP) cameras and/or TV systems

All types

All types

Types Maximum
continuous voltage
(L-N)
Maximum
discharge current
(8/20 μs)
Item no. Quantity SSU
PND-2in1-C-OS 255 V 10 kA 5081070
1 piece
Combined protection device 2in1 for CCTV camera systems
Combined protection device 2in1 for CCTV camera systems

Combined protection device 2in1 for CCTV camera systems

Item no. 5081070

Data sheet, 0.24MB, pdf
Download

Technical data

Temperature range -20 - +80 °C
Installation type Installation
Protection rating IP20
Earthing via: Connection cable / DIN rail
Lightning protection zone LPZ 1→3
SPD to IEC 61643-11 Class II+III
SPD to EN 61643-11 Type 2+3
Maximum continuous voltage (L-N) 255 V
Rated current 16 A
Protection level <1,3 kV
Idle voltage 10 kV
Nominal discharge current (8/20 µs) 5 kA
Maximum discharge current (8/20 μs) 10 kA

Dimensions

Length 122.5 mm
Width 100 mm
Height 37.1 mm

Network

Maximum continuous voltage AC 5.65 V
Maximum continuous voltage DC 8 V
SPD to IEC 61643-21 Class I+II+III / D1+C2+C1
Category Type 1+2+3 / D1+C2+C1
Impulse durability wire-wire C1: 0,3 kV / 0,15 kA (8/20µs)
Impulse durability wire-earth C2: 3 kV / 1,5 kA (8/20µs)
Impulse current (10/350) 0.5 kA
Protection level wire-wire <40 V
Protection level wire-earth <450 V
Frequency range 0 - 100 MHz
Frequency range 0 - 100 MHz
Cut-off frequency 100 MHz
Shielding connection available Yes
Shield connection Direct
Testing standard IEC 61643-21
3D data
Invitation to tender text

Invitation to tender text

PND-2in1-C-OS / 5081070
Download
Downloads

Data sheet

PND-2in1-C-OS / 5081070, 0.24MB, pdf
Download

Catalogues & Flyers

Surge protection for closed-circuit television systems (CCTV), 1.42MB, pdf
Download
PND surge protection device for CCTV, 0.14MB, pdf
Download

Instructions and Aid

Surge protection made easy – TBS selection aid, 0.88MB, pdf
Download
Surge protection selection aid, 2.65MB, pdf
Download
Lightning protection guide, 25.41MB, pdf
Download