CombiController V20 6-polig + NPE with remote signaling

Item no. 5095357 | EAN 4012196536979

  • 5-year warranty
  • Protection device to DIN EN 61643-11 or IEC 61643-11
  • Communautés Européennes, EC declaration of conformity according to EC directives
  • EurAsian Conformity
  • Transition from LPZ 1 to LPZ 2
  • Remote signalling
  • Halogen-free; without chlorine, fluorine and bromine
  • Installation electrotechnical expertise

Surge arrestor, type 2

• For surge voltage protection equipotential bonding to VDE 0100-443 (IEC 60364-4-44)
• Modular connectable arrestor with dynamic cut-off unit and visual status display
• Locking mechanism with vibration protection and voltage keying
• Halogen-free plastic (UL 94 V-0)
• The remote signalling variants (FS) have a potential-free changeover contact for remote signalling

Application: Equipotential bonding in main and sub-distributions.

All types

All types

Types Highest
continuous
voltage
AC
Pole
version
Protec-
tion
rating
Item no. Quantity SSU
V20-6+NPE+FS 280 V Other IP20 5095357
1 piece
CombiController V20 6-polig + NPE with remote signaling
CombiController V20 6-polig + NPE with remote signaling

CombiController V20 6-polig + NPE with remote signaling

Item no. 5095357

Data sheet, 0.36MB, pdf
Download

Connectivity options

SPD to EN 61643-11 Type 2
SPD to IEC 61643-11 Class II
SPD to UL 1449 Type 4
Nominal voltage AC (50/60 Hz) 230 V
Maximum continuous voltage AC 280 V
Nominal discharge current (8/20 µs) 20 kA
Maximum discharge current (8/20 μs) 40 kA
Arrestor surge current (8/20 µs) [total] 60 kA
Protection level [L-N] 1.3 kV
Residual voltage [L-N] @ 1 kA 0,8 kV
Residual voltage [L-N] @ 5 kA 1,0 kV
Max. mains-side overcurrent protection 160 A gL/gG
Short-circuit withstand for max. mains-side overcurrent protection 50 kA eff
Operating temperature range -40 - +80 °C
Protection rating IP20
FM contacts Changeover
Switching power AC 230 V; 0,5 A
Switching power DC 230 V; 0,1 A / 75 V; 0,5 A
Connection cross-section, FM terminals 0,5 - 1,5 mm²
Connection cross-section, FM terminals 21 - 16 AWG
Conductor cross-section, flexible (fine-wire) 1.5 - 35 mm²
Conductor cross-section, rigid (single wire/multi-wire) 1.5 - 35 mm²
Conductor cross-section, flexible (fine-wire) 16 - 2 AWG
Conductor cross-section, rigid (single wire/multi-wire) 16 - 2 AWG
TOV voltage [L-N] ‒ fail safe mode ‒ 120 min. 440 V
TOV voltage [L-N] ‒ withstand mode ‒ 5 s 335 V
TOV voltage [N-PE] ‒ withstand mode ‒ 200 ms 1200 V

Dimensions

Installation dimensions (LxWxH) 90x71,2x78,5 mm
Size 7 part units
Minimum distance 1.5 mm